Accessories (overview)
Motor holding brake control modules
Safety instructions for the installation according to UL/CSA
8
449
EDS94SPP101 EN 10.2
8.7.3 Safety instructions for the installation according to UL/CSA
Original − English
E94AZHX0051, E94AZHA0051
Warnings!
ƒ Only for use with series E94.
ƒ Secondary circuit shall supplied from an external isolating source.
ƒ Load at "Brake Output" is provided for "dc pilot duty".
ƒ The voltage rating of the fuses must at least be suitable for the input
voltage of the device.
ƒ Use 60/75 °C wire, except for control circuits.
ƒ Maximum surrounding air temperature: 55 °C.
ƒ These products are intended for use in a pollution degree 2 environment.
E94AZHY0101, E94AZHA0101, E94AZHY0025, E94AZHN0025, E94AZHY0026,
E94AZHN0026
Warnings!
ƒ Only for use with series E94.
ƒ Secondary circuit shall supplied from an external isolating source.
ƒ Load at "Brake Output" is provided for "dc pilot duty".
ƒ The voltage rating of the fuses must at least be suitable for the input
voltage of the device.
ƒ E94AZHx0101, E94AZHx0025:
– Use 105 °C wire only (min. wire size 20 AWG), except for control circuits.
ƒ E94AZHx0026:
– Use 60/75 °C wire only (min. wire size 20 AWG), except for control circuits.
ƒ Maximum surrounding air temperature: 55 °C.
ƒ These products are intended for use in a pollution degree 2 environment.
Branch circuit/short circuit protection with fuses in accordance with UL248
Type Fuse [A]
E94AZHX0051 7.5
E94AZHA0051 7.5
E94AZHY0101 7.5
E94AZHB0101 7.5
E94AZHY0025 5
E94AZHN0025 5
E94AZHY0026 5
E94AZHN0026 5