DC−bus operation
Rated data
DC−power requirements
7
347
EDS94SPP101 EN 10.2
7.4.3 DC−power requirements
Use the below tables to determine the power requirements of the devices used in the DC
bus and the device−dependent power loss for the rated mains voltage U
Lr
.
Use the below tables to determine the power requirements of the devices used in the DC
bus and the device−dependent power loss for the rated mains voltage U
Lr
.
Power requirements P
ar
[W] with rated current
Type U
Lr
= 230 V U
Lr
= 400 V U
LN
= 480 V
Multi Drives
E94AMxE0024
500 900 1000
E94AMxE0034 900 1600 1600
E94AMxE0044 1400 2500 2600
E94AMxE0074 2500 4400 4600
E94AMxE0094 3300 5800 6100
E94AMxE0134 4700 8100 8500
E94AMxE0174 5900 10300 10800
E94AMxE0244 8400 14700 15400
E94AMxE0324 11500 20000 19400
E94AMxE0474 16900 29300 30800
E94AMxE0594 19000 33100 38600
Single Drives
E94ASxE0024 500 900 1000
E94ASxE0034 900 1600 1600
E94ASxE0044 1400 2500 2600
E94ASxE0074 2500 4400 4600
E94ASxE0134 4700 8100 8500
E94ASxE0174 5900 10300 10800
E94ASxE0244 8400 14700 15400
E94ASxE0324 11500 20000 21000
E94ASxE0474 16900 29300 30800
E94ASxE0594 19000 33100 38600
E94ASxE0864 30800 53600 56300
E94ASxE1044 37300 64800 68100
E94BSxE1454 − 90000 100000
E94BSxE1724 − 107000 129000
E94BSxE2024 − 126000 151000
E94BSxE2454 − 153000 183000
E94BSxE2924 − 182000 218000
E94BSxE3664 − 228000 274000
E94BSxE4604 − 287000 344000
Tab. 7−6