4.4.6 Overcurrent operation
The controllers are designed for two overcurrent modes.
A load period must be followed by a recovery time. During the recovery time the current
must not exceed the value given.
The values given refer to the rated output current I
aN8
.
t
0
100
I [%]
aN8
t
1
t
2
t
3
t
4
9400SSP008
Fig. 4−1 Overcurrent capacity at 45° C
E94ASxE0024 ... E94ASxE1044
E94AMxE0024 ... E94AMxE0594
E94BSxE1454 ... E94BSxE4604
5 s cycle
–t
1
= 0.5 s load time with peak current
–t
2
= 4.5 s recovery time with limited current
1−min cycle
–t
1
= 10 s load time with peak current
–t
2
= 50 s recovery time with limited current
3−min cycle
–t
3
= 60 s load time with peak current
–t
4
= 120 s recovery time with limited current
3−min cycle
–t
3
= 60 s load time with peak current
–t
4
= 120 s recovery time with limited current