Single−axis controllers
Wiring
Safety instructions for the installation according to UL/CSA
3
111
EDS94SPP101 EN 10.2
Device sizes 81 and 82
Proceed as follows to disconnect the internal connection between the filters and PE:
1. The bridge that connects the filter with the protective earth can be found at the
indicated position.
2. Loosen both screws (do not remove them).
3. Fold the bridge downwards clockwise by 90°.
4. Tighten both screws .
– Starting torque: 3.4 Nm (30 lb−in)
94ITSW8001