Single−axis controllers
Wiring
Device 292 A (150 kW)
3
135
EDS94SPP101 EN 10.2
Mains
Terminal X100 Labelling Description
L1 L2 L3
A A A
L1
L2
L3
Connection of phases L1, L2, L3 with ring cable lug for M10 ().
SSP94KL191
Terminal data
Max. conductor cross−section Tightening torque
[mm
2
] [AWG] [Nm] [lb−in]
L1, L2, L3, flexible 240 500 mcm 47 416 SW17
Labelling Description
A
Connection for protective conductor (PE) with ring cable lug for M8
().
SSP94KL191
Terminal data
Max. conductor cross−section Tightening torque
[mm
2
] [AWG] [Nm] [lb−in]
− − 8 71 −