Single−axis controllers
Wiring
Devices in the range 366 ... 460 A (190 ... 240 kW)
3
143
EDS94SPP101 EN 10.2
Mains
Terminal X100 Labelling Description
A
L1 L2 L3
A A
L1
L2
L3
Connection of the phases L1, L2, L3 with ring cable lug for M16 ().
Connection for the PE conductor on the supply side with ring cable
lug for M10 ().
SSP94KL0X9
Note!
For mounting the cables, you need an extra large spanner socket.
Terminal data
Max. conductor cross−section Tightening torque
[mm
2
] [AWG] [Nm] [lb−in]
U, V, W, flexible 300 600 mcm 35 315 SW24
150 300 mcm 20 180 SW17
DC bus and external brake resistor
Terminal X104.1/X104.2 Labelling Description
A
A
B
A
+UG/Rb1
−UG
Rb2
Connection of DC−bus voltage and external brake resistor with ring
cable lug M10 ().
In case of double assignment, use sleeve from the scope of supply.
SSP94KL8x
Terminal data
Max. conductor cross−section Tightening torque
[mm
2
] [AWG] [Nm] [lb−in]
flexible 2 x 240 2 x 500 mcm 56 500
Inbus 10 or
SW17