Single−axis controllers
Control terminals
3
152
EDS94SPP101 EN 10.2
Analog inputs, analog outputs
The controller features two analog inputs which are able to detect differential voltage
signals in the range ±10 V, e.g. an analog speed setpoint selection or the voltage signal of
an external sensor (temperature, pressure, etc.).
ƒ The analog signal 1 can also detect a current setpoint.
The controller features two analog outputs, which can output internal analog signals as
voltage signals, e.g. for the control of analog indicating instruments or as a setpoint for
slave drives.
Electrical data
Analog input 1
Analog input 2
Level:
−10 ... +10 V
Resolution: 11 bits + sign
Scaling: ±10 V ±2
30
Conversion rate: 1 kHz
Analog input 1 as current input
(A1R and A1− bridged)
Level: −20 ... +20 mA
Resolution: 10 bits + sign
Scaling:
For C00034 = "1"
−20 ... −4 mA −2
30
... 0
+4 ... +20 mA 0 ... +2
30
For C00034 = "2"
±20 mA ±2
30
Conversion rate: 1 kHz
Open−circuit monitoring: Configurable
Analog output 1
Analog output 2
Level: −10 ... +10 V
(max. 2 mA)
Resolution: 11 bits + sign
Scaling: ±10 V ±2
30
Conversion rate: 1 kHz