Power supply modules
Rated data
Fuses and cable cross−sections
5
250
EDS94SPP101 EN 10.2
Operation without external mains choke/mains filter, installation according to
EN 60204−1
The data are recommendations. Other dimensioning/laying systems are possible (e.g.
according VDE 0298−4).
The cable cross−sections apply under the following conditions:
ƒ Use of PVC−insulated copper cables
ƒ Conductor temperature < 70 °C, ambient temperature < 45°C
ƒ No bundling of cables or cores
ƒ Three loaded cores
Type L1, L2, L3 − laying system FI
1)
B2 C F
[A] [A] [mm
2
] [mm
2
] [mm
2
] [mA]
E94APNE0104 C16 − 2.5 2.5 − 300
E94APNE0364 C40 − 10.0 10.0 − 300
E94APNE1004 − 125 − 50 50 300
E94APNE2454
−
315
−
− 150
(2 x 70)
300
Circuit breaker
Fuse of the utilisation category gG/gL or semiconductor fuses or the utilisation category gRL
1)
Universal−current−sensitive earth−leakage circuit breaker, RCD type B
If several devices or cable lengths > 50 m are used, it is possible that the circuit breaker will respond, depending on
the type of cable and the switching frequency.
2)
Device with integrated mains choke
Observe national and regional regulations!
Operation without external mains choke/mains filter, installation according to UL
Only use UL−approved cables, fuses and fuse holders.
UL fuse: Voltage 600 V; CC, J or T class fuses
Type standard installation motor group installation FI
1)
L1, L2, L3 L1, L2, L3
[A] [AWG] [A] [AWG] [mA]
E94APNE0104 15 14 15 14 300
E94APNE0364 60 6 60 6 300
E94APNE1004 125 1 125 1 300
E94APNE2454
300
350 mcm
2 x 1/0
300
350 mcm
2 x 1/0
300
Fuse
1)
Universal−current−sensitive earth−leakage circuit breaker, RCD type B
If several devices or cable lengths > 50 m are used, it is possible that the circuit breaker will respond, depending on
the type of cable and the switching frequency.
2)
Device with integrated mains choke
3)
The directive for a "group installation" according to UL508A or NEC, CEC must be considered.
Observe national and regional regulations!