Loading...
Regenerative power supply modules
General data and operating conditions
6
288
EDS94SPP101 EN 10.2
Environmental conditions
Climate
Storage IEC/EN 60721−3−1 1K3 (−25 ... +60 °C)
Transport IEC/EN 60721−3−2 2K3 (−25 ... +70 °C)
Operation IEC/EN 60721−3−3 3K3 (−10 ... +55 °C)
Current derating from +45 ... +55 °C: 2.5 %/°C
Site altitude 0 ... 4000 m amsl
1000 ... 4000 m amsl: current derating of 5 %/1000 m
Pollution EN 61800−5−1 Degree of pollution 2
Vibration resistance (9.81 m/s
2
= 1 g)
Transport
IEC/EN 60721−3−2 2M2
EN 61800−2
2 ... 9 Hz: Amplitude 3.5 mm
10 ... 200 Hz: acceleration resistant up to 10 m/s
2
200 ... 500 Hz: acceleration resistant up to 15 m/s
2
Operation
Germanischer Lloyd 5 ... 13.2 Hz: Amplitude ±1 mm
13.2 ... 100 Hz: acceleration resistant up to 0.7 g
IEC/EN 60068−2−6
10 ... 57 Hz: Amplitude 0.075 mm
57 ... 150 Hz: Acceleration resistant up to 1 g
Assignment of filters to standard devices
Note!
The operation of the regenerative power supply modules is only permissible
with an assigned mains filter.
Mains filter
Regenerative power supply module
Device size
Standard device Installation
backplane
E94AZMR0264SDB
E94AZMR0264LDB
E94ARNE0134
E94AZPP0364 GG3
E94AZMR0474SDB
E94AZMR0474LDB
E94ARNE0244
E94AZMR0xxSDB −> "short distance" E94AZMR0xxLDB −> "long distance"
General electrical data
Power loss P
V
[W]
Type Total (when operating with I
aN
) Constant (control electronics only)
E94ARNE0134 150 40
E94ARNE0244 230 40
Power loss Inductance Regenerative
inductance
Voltage drop
P
V
[W] L [mH] L
gen
[mH] U [V]
E94AZMR0264SDB 65
0.77 10 % 0.84 10 % 6.3
E94AZMR0264LDB 72
E94AZMR0474SDB 85
0.42 10 % 1.54 10 % 6.2
E94AZMR0474LDB 101

Table of Contents