Single−axis controllers
General data and operating conditions
3
38
EDS94SPP101 EN 10.2
Max. shielded motor cable lengths for compliance with the
conducted interference emission according to C3
Type with RFI filter with mains filter without filter
E94BSxE1454 − − 150 m
E94BSxE1724 − − 150 m
E94BSxE2024 − − 150 m
E94BSxE2454 − − 150 m
E94BSxE2924 − − 150 m
E94BSxE3664 − − 150 m
E94BSxE4604 − − 150 m
Longer motor cables can be achieved when line filters are used in combination with
sinusoidal filters. Further conditions to be observed:
ƒ V/f control mode
ƒ Switching frequency is permanently set (C00018)
Max. motor cable lengths for compliance with the conducted interference emission according to C2 when
sinusoidal filters and line filters are used
Type
RFI filter Mains filter Sine filter shielded
unshielded
Switching
frequency
E94ASxE0024
−
E94AZMS0034 EZS3−004A200
100 m
300 m
4 kHz
or
8 kHz
E94ASxE0034
E94ASxE0044
−
E94AZMS0094 EZS3−010A200
E94ASxE0074
E94ASxE0134
− E94AZMS0184 EZS3−024A200
E94ASxE0174
E94ASxE0244 − E94AZMS0314 EZS3−037A200
E94ASxE0324
E94AZRS0544 −
EZS3−048A200
150 m
300 m
4 kHz
or
8 kHz
E94ASxE0474 EZS3−061A200
E94ASxE0594 EZS3−072A200
E94ASxE0864
E94AZRS0954 −
EZS3−115A200
150 m
300 m
2 kHz
or
4 kHz
E94ASxE1044 EZS3−150A200
E94BSxE1454
E94AZRS1804
3F480−180.290EM
− EZS3−180A200
150 m
− m
2 kHz
or
4 kHz
E94BSxE1724
E94AZRS1804
3F480−180.290EM
− EZS3−250A200
E94BSxE2024
E94AZRS3004
3F480−300.290EM
− EZS3−250A200
E94BSxE2454
E94AZRS3004
3F480−300.290EM
− EZS3−350A200
E94BSxE2924
E94AZRS3004
3F480−300.290EM
− EZS3−350A200
E94BSxE3664
E94AZRS4154
3F480−415.290EM
− EZS3−480A200
E94BSxE4604
E94AZRS4154
3F480−415.290EM
−
EZS3−350A200
(2 in parallel)
Tab. 3−3
EMC limit classes of the conducted interference emission in TN/TT systems:
C2 according to EN 61800−3, corresponds to class A according to EN 55011