EasyManua.ls Logo

Lenze L-force 9400 - Page 388

Lenze L-force 9400
646 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Accessories (overview)
Communication modules
Ethernet interface
8
388
EDS94SPP101 EN 10.2
DescriptionColour / statusLED
redgreen
LED
MS blinking off
250 ms
250 ms
CIP module status: "Standby"
The communication module has not been configured completely or the
configuration is faulty.
blinking blinking
250 ms
250 ms
CIP module status: "Device Self Testing"
The communication module is performing a self test.
NS
off off CIP network status: "No IP Address"
The communication module is not supplied with voltage or has not received
an IP address yet.
off on
CIP network status: "Duplicate IP"
The communication module cannot access the fieldbus (IP address conflict).
off blinking
250 ms
250 ms
CIP network status: "Connection Timeout"
A time−out has occurred.
on off
CIP network status: "Connected"
The communication module operates correctly and is connected to the
scanner.
blinking off
250 ms
250 ms
CIP network status: "No Connections"
The communication module ...
operates correctly;
has been assigned with an IP address;
has not been integrated yet into the network by the scanner.
blinking blinking
250 ms
250 ms
CIP network status: "Self−Test"
The communication module is performing a self test.