Accessories (overview)
Filters
Mains filters for regenerative power supply modules E94AZMRxxxx (26 ... 47 A)
8
561
EDS94SPP101 EN 10.2
Protection of persons and equipment
Enclosure
EN 60529 IP20
Not in the wire range of the
terminals
NEMA 250 Protection against contact
to type 1
Earth leakage current IEC/EN 61800−5−1 > 3.5 mA AC
> 10 mA DC
Observe regulations and safety
instructions!
Insulation resistance IEC/EN 61800−5−1
< 2000 m site altitude: overvoltage category III
> 2000 m site altitude: overvoltage category II
Environmental conditions
Climate
Storage
IEC/EN 60721−3−1 1K3 (−25 ... +60 °C)
Transport IEC/EN 60721−3−2 2K3 (−25 ... +70 °C)
Operation IEC/EN 60721−3−3 3K3 (−10 ... +55 °C)
Current derating from +45 ... +55 °C: 2.5 %/°C
Site altitude 0 ... 4000 m amsl
1000 ... 4000 m amsl: current derating of 5 %/1000 m
Pollution EN 61800−5−1 Degree of pollution 2
Vibration resistance (9.81 m/s
2
= 1 g)
Transport
IEC/EN 60721−3−2 2M2
EN 61800−2
2 ... 9 Hz: Amplitude 3.5 mm
10 ... 200 Hz: acceleration resistant up to 10 m/s
2
200 ... 500 Hz: acceleration resistant up to 15 m/s
2
Operation
Germanischer Lloyd 5 ... 13.2 Hz: Amplitude ±1 mm
13.2 ... 100 Hz: acceleration resistant up to 0.7 g
IEC/EN 60068−2−6
10 ... 57 Hz: Amplitude 0.075 mm
57 ... 150 Hz: Acceleration resistant up to 1 g
Mounting conditions
Mounting place
In the control cabinet
Mounting position Vertically
Free space The required free space results from the mounting position
and the specifications of the standard device.
Rated data
Mains Voltage Voltage range Frequency range
U
Lrated
[V] U
Lrated
[V] f [Hz]
3/PE AC 230 180 − 0 % ... 264 + 0 % 45 − 0 % ... 65 + 0 %
3/PE AC 400 320 − 0 % ... 440 + 0 % 45 − 0 % ... 65 + 0 %
3/PE AC 500 400 − 0 % ... 550 + 0 % 45 − 0 % ... 65 + 0 %
Voltage Freq. Current [A] Current [A]
Number of
phases
[V] [Hz] max. +45° C max. +55° C
E94AZMR0264xDB 230/400/500 50/60 26/26/26 19/19/19 3
E94AZMR0474xDB 230/400/500 50/60 47/47/47 35/35/35 3
Temperature in the control cabinet