Accessories (overview)
General accessories
Brake resistors
8
622
EDS94SPP101 EN 10.2
Power supply
module
Brake resistor
Resistance Continuous power Quantity of heat
R [] P [W] QB [kWs]
E94APNE0104
ERBP027R200W
27
200 30
ERBS027R600W
600 90
ERBS027R01K2
1200 180
E94APNE0364
ERBG012R01K9
12
1900 285
ERBG012R05K2
5200 780
E94APNE1004 ERBG005R02K6 5 2600 390
E94APNE2454 ERBG028D04K1 2.8 4100 615
Regenerative
power supply
module
Brake resistor
Resistance Continuous power Quantity of heat
R [] P [W] Q
B
[kWs]
E94ARNE0134
ERBP027R200W
27
200 30
ERBS027R600W
600 90
ERBS027R01K2
1200 180
E94ARNE0244
ERBP018R300W
18
300 30
ERBS018R01K2
1200 180
ERBS018R02K8 2800 420
Operating conditions
Climatic
conditions
Class 3K3 to EN 50178 Without condensation, average relative humidity
85 %
Ambient
temperature
−10 °C ... +55 °C
Above 45 °C the permanent power P
d
is to be reduced by 2.5 %/°C
Installation
height
0 ... 4000 m amsl
Above 1000 m the permanent power P
d
is to be reduced by 5 %/1000 m
Mounting
location
The mounting location must comply with the device features mentioned in the chapter
"General data".
Flammable materials or substances must not be placed in the vicinity of the brake
resistor.
The heat generated by the brake resistor must be dissipated freely.
Mounting
position
Standard Vertically suspended with connecting cables at the bottom.
Variant Horizontally standing with fixing bracket at the bottom.
The permanent power P
d
is to be reduced by 30 %!
Free spaces
Standard at the top > 200 mm, to the sides > 25 mm, at the bottom > 100 mm
Variant at the top > 200 mm, to the sides > 45 mm, at the bottom > 45 mm
Design and
project planning
Mean value of regenerative power < permanent power P
d
of brake resistor.
Regenerative power during braking time < heat quantity Q
B
of brake resistor.
Braking time < 10 % of cycle time (braking time + dead time).
Always connect the thermal contact and integrate it in a way into the system monitoring
that the mains supply will be switched off when the basic device is overheated.