Single−axis controllers
Wiring
Important notes
3
98
EDS94SPP101 EN 10.2
Stop!
No device protection if the mains voltage is too high
The mains input is not internally fused.
Possible consequences:
ƒ Destruction of the device if the mains voltage is too high.
Protective measures:
ƒ Observe the maximally permissible mains voltage.
ƒ Fuse the device correctly on the supply side against mains fluctuations and
voltage peaks.
Stop!
Overvoltage on components:
On IT systems an earth fault in the installation can cause impermissible
overvoltages.
Possible consequences:
Destruction of the device.
Protective measures:
If the devices are operated on IT systems, the internal connection of the filters
to the protective earth in the installation backplane has to be disconnected
( 108).
Note!
Switching operations on the motor side of the controller are permitted for
safety switch−off (emergency off).
Please observe:
ƒ When the controller is enabled, switching operations may lead to a response
of the controller monitoring functions.
ƒ The switching elements on the motor side must be rated for DC voltages
with U
DCmax
= 800 V.