Lenze · E94AYCER communication module (PROFINET®) · Communication Manual · DMS 11.0 EN · 04/2016 · TD17 99
14 Parameter reference
14.2 Parameters of the communication module for slot MXI1
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13879
C13880
C13881
C13882
Parameter | Name:
C13879 | Bus error
Data type: UNSIGNED_32
Index: 10696 = 0x29C8
Display of the error currently detected on the fieldbus.
Display range (min. value | unit | max. value)
0 4294967295
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Value Meaning
0No error
3481402629 The PROFINET communication link has been interrupted.
Parameter | Name:
C13880 | Monitoring Reaction
Data type: UNSIGNED_8
Index: 10695 = 0x29C7
The action set in subcode 1 is executed when the node detects that it is no longer in the "Data_Exchange" state.
• Please also observe the notes provided in code C13881
.
• A change in the monitoring response becomes immediately effective.
Interruption of PROFINET communication
( 77)
Selection list
0 No response
1Fault
3 Quick stop by trouble
4 Warning Locked
6 Information
Subcodes Lenze setting Info
C13880/1 0: No Response
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13881 | Response time when exiting "Data_Exchange"
Data type: UNSIGNED_16
Index: 10694 = 0x29C6
If the "Data_Exchange" status is exited, the response parameterised in C13880 is activated after the time set here
has expired.
• A value of "65535" in this code deactivates the monitoring function.
• A change in the monitoring response becomes immediately effective.
Setting range (min. value | unit | max. value) Lenze setting
0 ms 65535 0ms
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13882 | Display: Monit. time: Watchdog
Data type: UNSIGNED_32
Index: 10693 = 0x29C5
Display of the watchdog monitoring time specified by the IO controller
Note: This code will not be supported anymore from SW version 2.10 for reasons related to the system.
Display range (min. value | unit | max. value)
0 4294967295
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT