Installation
64 ODSL 30 Leuze electronic
Error messages
Rapid flashing of the green LED following a teach event indicates an unsuccessful teach
event. The sensor remains ready for operation and continues to function with the old values.
Remedy:
• Repeat teach event or
• Activate teach input for more than 8s or
• Disconnect sensor from voltage to restore the old values.
Teach procedure for ODSL 30/D… (2 switching outputs)
Position the measured object at the first desired distance. Connect the teach input
teach Q1/Q2 for 2sec. to +U
B
. The LEDs are flashing simultaneously. Reconnect the
teach input to GND. The first switching output is taught.
Now, position the measured object at the second desired distance. Connect the teach
input teach Q1/Q2 for 2sec. to +U
B
. The LEDs now flash alternately. Reconnect the
teach input to GND. The second switching output is taught. In non-operational mode,
the teach input is connected to GND.
Teaching takes place towards the switching points.
These default values are preset:
• Function characteristics of the switching outputs: "light switching"
• Lower switching point Q1: 199mm, lower switching point Q2: 199mm
• Upper switching point Q1: 1000mm, upper switching point Q2: 1500mm
• Hysteresis: 20mm each
You can change these values using the keypad and LC display.
Teach procedure for ODSL 30/24… (3 switching outputs)
Switching outputs Q1/Q2: Teach procedure is the same as for ODSL 30/D…
Switching output Q3: Teach procedure is the same as for ODSL 30/V… via teach input
teach Q3
Teaching takes place towards the switching points.
These default values are preset:
• Function characteristics of the switching outputs: "light switching"
• Lower switching point Q1: 199mm, lower switching point Q2: 199mm,
lower switching point Q3: 199mm
• Upper switching point Q1: 1000mm, upper switching point Q2: 1500mm,
upper switching point Q3: 2000mm
• Hysteresis: 20mm each
You can change these values using the keypad and LC display.