98 THE BLUE BOX LT SYSTEM START-UP & CABLING GUIDE
LCDBBSSU&CG03Sept08
HARDWARE ACTIvATION TESTS
Before starting, note total approximate bus cable length:
Once each cable has been checked with a LAN cable tes-
ter and plugged-in, it is still possible for the entire connect-
ed cable structure to become problematic. For instance,
dirt may accumulate inside the RJ45 sockets, the strain
on the Cat. 5 when pushing switches into the wall may
weaken connections or even break the conductors, or the
bus length may exceed 4000 ft.
Each test must be passed before moving onto the next. If
any readings are out of range, refer to “Hardware Activa-
tion Troubleshooting” section at the end of this document
or call Technical Support at 1-800-345-4448.
CONTINUITY TEST
This test is intended to verify bus length, continuity, and
detect crossed data-pair wires.
De-power every item on the bus and check the volt-1.
age at both ends to ensure a reading of 0vdc. Re-
move any terminators.
At one end of the bus, plug in the “Data/Power Jumper. 2.
At the other end of the bus, plug in the “Bus Checker Card” 3.
and measure resistance across the following terminals:
Gnd to A ____ohms B to +12 ____ohms
All test values must be within 10% of the values in the 4.
chart below to be considered valid!
Length Ohms Length Ohms
100 ft. 3 to 6 2000 ft. 68 to 80
500 ft. 12 to 20 3000 ft. 102 to 120
1000 ft. 34 to 40 4000 ft. 130 to 160
Continuity Test Results (Gnd to A & B to +12)
SHORT CIRCUIT TEST
This test is intended to detect any short circuits along the
bus. Please use the lowest resistance range (200 ) setting
on your multi-meter. DO NOT use a “beep” test.
Remove the “Data Power Jumper” and measure the 5.
resistance across the following terminals on the “Bus
Checker Card,
All test values should be greater than 1K ohm! 6.
Gnd to A ____ohms A to B ____ohms
Gnd to B ____ohms A to +12 ____ohms
Gnd to +12 ____ohms B to +12 ____ohms
EARTH GROUND TEST
This test is intended to detect any pathways to earth
ground.
Measure resistance between the terminals mentioned be-7.
low, and “Earth ground” (a metallic enclosure or conduit).
Gnd A
+12 B
All readings between each terminal and “Earth 8.
ground” should be infinite or “Open”!
TERMINATOR TEST
This test is intended to ensure that only 2 terminators
exist, one at each end of the bus. If the readings are out of
range, it would indicate a missing, misplaced, or an extra
terminator (terminators are shipped in the Master Panel).
Add a “Terminator” on the first and last device. On 9.
the “Bus Checker Card“, measure
A to B ____ohms
Test reading should be within 62 10.
to 92 !
Remove the bus checker card and call our Tech Sup-11.
port with your results at: 1-800-345-4448 x391.
Bus Checker Card
Figure A:
Data/Power Jumper

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lighting Controls Blue Box LT Series and is the answer not in the manual?

Lighting Controls Blue Box LT Series Specifications

General IconGeneral
BrandLighting Controls
ModelBlue Box LT Series
CategoryController
LanguageEnglish