Chapter 7. Function List
Display Name
Min/Max
range
Description
Factory
defaults
during
P38
Number of
Auto
Restart try
0 ~ 10
It sets the number of restart tries
after a fault occurs. Auto Restart is
deactivated if the fault outnumbers
the restart tries. This function is
active when [drv] is set to 1 or 2
{Run/Stop via control terminal}.
0
1)
O
P39
Restart
0 ~ 60
[sec]
Restart tries after auto restart
waiting time has passed.
1.0 O
P40
Selects the capacity of a motor to
use.
2)
X
P41
motor
2 ~ 12
It is displayed via rpm in drive
group.
4 X
P42
Rated slip
frequency
0 ~ 10
[Hz]
Enter the difference between the
input power frequency and the
value calculated by converting rpm
described in the nameplate to
3)
X
P43
rated
0.0~ 25.5
[A]
Enter motor rated current on the
nameplate.
- X
P44
No Load
Motor
Current
0.0 ~
25.5 [A]
Enter the current value detected
when the motor is rotating in rated
rpm after the load connected to
the motor shaft is removed.
Enter the 50% of the rated current
value when it is difficult to
measure No Load Motor Current.
- X
P45
Carrier
frequency
select
1 ~ 10
[kHz]
It selects the audible sound of the
motor. If the set value is higher,
the inverter sound is quieter but
the noise from the inverter and
leakage current will become
3 O
1)
No auto restart in case of protection functions such as OHt, Lvt, ESt, HWt.
2)
P40 initial value is preset based on inverter rating.
3)
P42 ~ P44 values are changed based on the P40. factory defaults are set based
on the inverter capacity.