Chapter 7. Function List
7-1
7. Function List
Display
Name
Min/Max
range
Description
Factory
defaults
Adj.
during
run
0.0
Frequency
command
0 ~ 200
[Hz]
This parameter sets the operation
frequency. During stop, it displays
Frequency Command; During run, it
shows output frequency. During multi-
step operation, it becomes frequency
0. It cannot be set greater than Max
frequency(P16).
0.00 O
ACC Acc time
0 ~
6000
[sec]
During multi-acc/dec operation, this
parameter serves as acc/dec time 0.
5.0 O
dEC Dec time 10.0 O
drv Drive mode 0 ~ 3
0
Operate with RUN/STOP key of the
loader
1 X
1
Terminal
operation
FX: forward run
RX: reverse run
2
FX: Run/stop command
RX: Reverse rotation
3
communication: communication
option
Frq
Frequency
setting
method
0 ~ 4
0
Digital
Set loader digital
frequency 1
0 X
1
Set loader digital
frequency 2
2
Analogue
Terminal AI input
3
Loader volume
resistance
4
communication option
St1
Multi-step
frequency 1
0 ~ 200
[Hz]
Set multi-step frequency 1 10.00 O
St2
Multi-step
frequency 2
Set multi-step frequency 2 20.00 O
St3
Multi-step
frequency 3
Set multi-step frequency 3 30.00 O

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LS Industrial Systems SV-iE5 Series and is the answer not in the manual?

LS Industrial Systems SV-iE5 Series Specifications

General IconGeneral
BrandLS Industrial Systems
ModelSV-iE5 Series
CategoryInverter
LanguageEnglish

Related product manuals