8-6
When F65 is 1: It is increased as many as step frequency set as F66 at the rising edge of multi-
function input set as UP and when up-down is defined, it saves frequency at the falling edge. It
is decreased as many as step frequency set as F66 at the falling edge of rising edge of multi-
function input set as DOWN and when up-down is defined, it saves frequency as the falling
edge. In this case, while multi-function input set as UP or DOWN is defined, if stop command is
inputted, previous falling edge value is saved and if multi-function input is not defined, present
frequency is not saved. The accel/decel time is same with when stetted as “0”.
When F65 is 2: It is increased as many as step frequency set as F66 at the rising edge of multi-
function input set as UP and if it is activated for 3 second, it operates like something set as “0”.
It is decreased as many as step frequency set as F66 at the rising edge of multi-function input
set as DOWN and if it is activated for 3 second, it operates like something set as “0” and the
accel/decel time is same with when stetted as “0”.
CAUTION
Because of UP or DOWN, when the input is entered again before it is increased as
many as 1 step frequency, the input is ignored and the saved frequency is also
frequency of the inactivated moment