Page #53 background imageLoading...
Page #53 background image
5-8
z Function group 1
LED
display
Address
for
commun
ication
Parameter
name
Min/Max
range
Description
Factory
defaults
Adj.
during
run
Page
F66
A242 [Up-down
step
frequency]
0~400[
Hz]
In case of choosing F65 as a 1 or 2, it means
increase or decrease of frequency according
to up-down input
0.00 X 8-5
F70
A246 [Draw run
mode
select]
0~3 0 Inverter doesn’t run as a draw
mode
0 X 8-28
1 V1(0~10V) input draw run
2 I(0~20mA) input draw run
3 V1(-10~10V) input draw run
F71
A247 [Draw rate] 0~100[
%]
Sets rate of draw 0.00 0 8-28