Chapter 7 Input/Output Specifications
7-47
7.3.15 XBC-DR40SU 16 point relay output
Model
Specification
Main unit
XBC-DR40SU
Output point
16 point
Insulation method
Relay insulation
Rated load
voltage/current
DC24V 2A (resistive load) / AC220V 2A (COS = 1), 5A/COM
Min. load voltage/current
DC5V / 1
Max. load voltage
AC250V, DC125V
Off leakage current
0.1 (AC220V, 60 )
Max. On/Off frequency
3,600 times / hour
Surge absorber
None
Service
life
Mechanical
20 million times or more
Electrical
Rated load voltage / Current 100,000 times or more
AC200V / 1.5A, AC240V / 1A (COS = 0.7) 100,000 times or more
AC200V / 1A, AC240V / 0.5A (COS = 0.35) 100,000 times or more
DC24V / 1A, DC100V / 0.1A (L / R = 7 ) 100,000 times or more
Response
time
Off On
10ms or less
On Off
12ms or less
Common method
4 point / COM (COM0~COM8), 8 point / COM (COM4~COM5)
Proper cable size
Stranded cable 0.3~0.75 (External diameter 2.8 or less)
Operation indicator
LED On when Output On
External connection
method
30 point terminal block connector (M3 X 6 screw)
Weight
594g
Circuit configuration
No.
Contact
No.
Contact
Type
TB1
AC100
~240V
TB2
FG
TB3
TB4
COM0
TB5
40
TB6
COM1
TB7
41
TB8
COM2
TB9
42
TB10
43
TB11
P
TB12
COM3
TB13
44
TB14
45
TB15
46
TB16
47
TB17
NC
TB18
COM4
TB19
48
TB20
49
TB21
4A
TB22
4B
TB23
NC
TB24
COM5
TB25
4C
TB26
4D
TB27
4E
TB28
4F
TB29
24V
TB30
24G
TB1
TB3
TB5
TB7
TB9
TB11
TB13
TB15
TB17
TB19
TB21
TB23
TB25
TB27
TB29
TB2
TB4
TB6
TB8
TB10
TB12
TB14
TB16
TB18
TB20
TB22
TB24
TB26
TB28
9
TB30
Terminal
block no.
R
Y
Internal circuit
L
L
E
D
TB5
TB4
R
Y
L
TB7
TB6
L
TB9
COM0
COM1
R
Y
TB8
L
COM2
TB10
R
Y
TB12
L
COM3
TB16
TB13
R
Y
TB24
L
COM5
TB28
TB25
www.behaotomasyon.com
www.behaotomasyon.com