8.1.4 “S(U)type Functions
(1) Counter mode
(a) High Speed counter module can count High Speed pulses which can not be processed by
CPU module’s counter instructions (CTU, CTD, CTUD, etc.), up to binary value of 32 bits (-
2,147,483,648 ~ 2,147,483,647).
(b) Available input is 1-phase input, 2-phase input and CW/ CCW input.
(c) Count increasing/decreasing methods are as follows;
1) For 1-phase input: a) Increasing/decreasing count operation by program setting
b) Increasing/decreasing count operation by B-phase input signal
2) For 2-phase input: setting by difference in phase between A-phase and B-phase
3) For CW/CCW input: Increasing operation if B-phase is LOW with A-phase input, and
Decreasing operation if A-phase is LOW with B-phase input.
(d) Auxiliary modes are as follows;
1) Count Latch
2) Count function about the number of revolution per unit time
(e) Pulse input mode
1) 1 phase count mode
a) Increasing/decreasing count operation by program setting
1-phase 1-input 1-multiplication operation mode
A-phase input pulse counts at rising and increasing/decreasing will be decided by the
applicable program.
Increasing/Decreasing classification
A-phase input pulse
rising
A-phase input pulse
falling
Increasing/decreasing count setting signal Off
Increasing count
-
Increasing/decreasing count setting signal On
Decreasing count
-
Operation example
A-phase input pulse
Increasing
Decreasing
Increasing
Increasing/Decreasing
count setting signal
Count value
10
11
12
13
12
11
10
11
On
Off
www.behaotomasyon.com
www.behaotomasyon.com