Chapter 3 General Specifications
3-1
Chapter 3 General Specifications
3.1 General Specifications
The General specification of XGB series is as below.
No.
Items
Specification
Reference
1
Ambient Temp.
0 ~ 55 C
-
2
Storage Temp.
25 ~ 70 C
3
Ambient humidity
5 ~ 95%RH (Non-condensing)
4
Storage humidity
5 ~ 95%RH (Non-condensing)
5
Vibration
resistance
Occasional vibration
-
Frequency
Acceleration
Amplitude
Times
IEC61131-2
10 f 57Hz
0.075mm
10 times
each
direction
(X,Y and Z)
57 f 150Hz
9.8m/s
2
(1G)
Continuous vibration
Frequency
Acceleration
Amplitude
10 f 57Hz
0.035mm
57 f 150Hz
4.9m/s
2
(0.5G)
6
Shock resistance
Peak acceleration : 147 m/s
2
(15G)
Duration : 11ms
Half-sine, 3 times each direction per each axis
7
Noise resistance
Square wave
impulse noise
AC: 1,500 V
DC: 900 V
LSIS standard
Electrostatic
discharge
Voltage: 4kV (Contact discharge)
IEC61131-2
IEC61000-4-2
Radiated
electromagnetic
field noise
80 ~ 1,000 MHz, 10V/m
IEC61131-2,
IEC61000-4-3
Fast transient
/Burst noise
Segment
Power supply
module
Digital/Analog Input/Output,
Communication Interface
IEC61131-2
IEC61000-4-4
Voltage
2kV
1kV
8
Environment
Free from corrosive gases and excessive dust
-
9
Altitude
Up to 2,000 ms
10
Pollution degree
2 or less
11
Cooling
Air-cooling
1) IEC (International Electrotechnical Commission):
An international nongovernmental organization which promotes internationally cooperated standardization in
electric/electronic field, publishes international standards and manages applicable estimation system related
with.
2) Pollution degree:
An index indicating pollution degree of the operating environment which decides insulation performance of the
devices. For instance, Pollution degree 2 indicates the state generally that only non-conductive pollution occurs.
However, this state contains temporary conduction due to dew produced.