3)
CW(Clockwise)/CCW(Counter Clockwise) operation mode
A-phase input pulse counts at rising , or B-phase input pulse counts at rising.
Increasing operation executed when B-phase input pulse is Low with A-phase input pulse at
rising, and Decreasing operation executed when A-phase input pulse is Low with B-phase
input pulse at rising.
Increasing/Decreasing
classification
A-phase input pulse High A-phase input pulse Low
B-phase input pulse High -
decreasing count
B-phase input pulse Low Increasing count -
Operation example
(2) Counter mode
2 types of count (Linear counter, Ring counter) can be selected for the applicable use based on
functions.
Counter mode is saved at the following special K area.
Mode
Area per each channel (word)
Ref.
Ch.0
Ch.1
Ch.2
Ch.3
Ch.4
Ch.5
Ch.6
Ch.7
Counter
mode
K300 K330 K360 K390 K2220 K2250 K2280 K2310
0 : linear
1 : ring
B-phase input pulse
Count value
A-phase input pulse
Increasing
Decreasing
7
8
9
10
11
9
8
10
7