Chapter 8 Analog Input Option Board (XBO-AD02A)
8.6.2 Count Averaging Function
The input values of the designated channel are accumulated for the preset cycles, and the average
value of the total sum is outputted in digital data.
(1/Ch)








Setting Range = 2 ~ 64000 [times]
For count averaging, averaging interval is calculated with the No. of channels used.
Averaging interval [ms] = Averaging count x (No. of channels used x1ms + Scan time)
Note
(1) Averaging interval varies according to scan time