10.6.3 Channel Output State Setting Function
It sets output against PLC stop and abnormal state
(1) Function
It is used to output an already set value when PLC system switches RUN to Stop
(2) Type
You can select one among former, min, middle and max value.
(a) Former value: keeps last normal output value
(b) Min. value: outputs minimum value of the each output range
(c) Middle value: outputs middle value of the each output range
(d) Max. value: outputs max. value of the each output range.
(3) Example
When output is 10mA and range of output channel is 4~20mA, if system switches Run to Stop,
it outputs as follows according to output state setting.
(a) Former value: keeps previous output, 10mA
(b) Min. value: outputs min. value of corresponding range, 4mA.
(c) Middle value: outputs middle value of corresponding range, 12mA
(d) Max. value: outputs max. value of corresponding range, 20mA.