ND30-09D 78 User's manual
V~
110 V~
230 V~
400 V~
11.000..22.000 ..132.00 V
23.000..46.000 .. 276.00 V
40.000..80.000 .. 480.00 V
...1920.0 kV
Voltage U L-L: 100 V~
190 V~
400 V~
690 V~
10.000 ..20.000..120.00 V
19.000 ..38.000..228.00 V
40.000..80.00 .. 480.00 V
69.000..138.00 .. 830.00 V
...1999.0 kV (tr_U≠1)
0.5 (EN 61557-12)
Active power P -19999 MW .. 0.000 W ..
..19999 MW
(tr_U≠1,tr_I≠1)
0.5 (EN 61557-12)
Reactive power Q -19999 MVar .. 0.000
Var ..
..19999 MVar
(tr_U≠1,tr_I≠1)
1 (EN 61557-12)
Apparent power S 0.000 .. 1999,9 VA ..
..19999 MVA
(tr_U≠1,tr_I≠1)
0.5 (EN 61557-12)
Active energy EnP
/ import or export /
0.000 .. 99 999 999.999
kWh
0,2S (EN 62053-22)
Reactive energy EnQ
/ capacity or inductive /
0.000 .. 99 999 999.999
kVarh
1
(EN 61557-12)
Apparent energy EnS 0.000 .. 99 999 999.999
kVAh
0.5 (EN 61557-12)
Active power factor PF -1.00 .. 0 .. 1.00 1 (EN 61557-12)
Factor tg -1.20 .. 0 .. 1.20 1
Frequency f 45.000 ..100.000 Hz 0.1 (EN 61557-12)
Harmonic distortion
factor of voltage THDU,
current THDI
0.0 .. 100.0% 5 (EN 61557-12)
Harmonic amplitudes of
voltage U
h2
...U
h51
,
of current I
h2
I
h51
0.0 .. 100.0% II (IEC61000-4-7)
tr_I - Current transformer ratio = Transformer primary current / Current
transformer secondary current
tr_U - Voltage transformer ratio = Transformer primary voltage / Voltage
transformer secondary voltage
Power consumption:
- in supply circuit
- in voltage circuit
- in current circuit
≤ 6 VA
≤ 0.5 VA
≤ 0.1 VA
Readout field 3.5’’ TFT full-color screen,
resolution: 320 x 240 pixel