Curve File Import/Export notes
As needed, import (load) or export (save) a thermistor or non-linear curve file in xml format using the
Import and Export buttons in either the Tabular Thermistor Dialog (Figure 3-20) for a
“Tabular Thermistor” conversion, or Tabular Conversion Dialog (Figure 3-13 on page 20) for a “Generic Tabular”
conversion.
When you do this, the standard Niagara File Chooser dialog appears, as shown in Figure 3-21.
Figure 3-21 File Chooser to locate thermistor or non-linear curve .xml file
To import a thermistor curve file, you can navigate to your “My Modules” folder, then to the xml folder in the kitIo
module (Jar) file (if available, see
Figure 3-21). If the kitIo module is not available, navigate to the xml folder in the
Ndio module (Jar) file.
Or, you can navigate to any other location you have a thermistor curve file. Import any other saved, custom non-
linear conversion .xml files the same waysee “Non-linear sensor support” on page 20.
As of the date of this document, the kitIo module contains an xml folder with five (5) different thermistor curves in
xml format, as follows:
precon_type_2_model_24.xml For Precon type 2 model 24 sensor
precon_type_4_model_42.xml For Precon type 4 model 42 sensor
rs271_0110.xml For Radio Shack sensor model 271-0110
te6300_10k For TE-6300 10K type sensor
type_3.xml For standard Type-3 Thermistor sensor
Note: Upon any curve file import, all existing thermistor or non-linear curve configuration for that Onyxx
Proxy point is overwritten by the imported file.
To export a curve .xml file, use the File Chooser to navigate to a location to save the current thermistor curve
configuration, and supply a File Name. The saved .xml file can be used in the configuration of any other Onyxx or
Ndio Proxy point, whether in this station or another station.