Quattro DC Drive A1 Submenu
45
Parameter Description Units Default Range
Hidden
Item
Run
lock
out
ZERO SPEED
LEVEL
(Zero Speed Level) This parameter sets
the threshold for zero speed detection.
This is only used to generate the zero
speed logic output.
Note: if DIR CONFIRM (C1) is enabled,
this parameter also sets the threshold for
the termination of the test to confirm the
polarity of the analog speed command.
Unites in percent of contract speed
% 1.00 0.00 – 99.99
Y Y
ZERO SPEED
TIME
(Zero Speed Time) This parameter sets
the time at which the drive is measured to
be at or below the ZERO SPEED LEVEL
(A1) before zero speed logic output is
true.
sec 0.10 0.00 – 9.99
Y Y
UP/DWN
THRESHOLD
(Directional Threshold) This parameter
sets the threshold for the direction sense
logic outputs. If speed feedback does not
reach this level, the drive will not detect a
directional change. This is only used to
generate the direction sense logic outputs
(car going up and car going down). Units
in percent of contract speed.
% 1.00 0.00 – 9.99
Y Y
ANA 1 OUT
OFFSET
(Digital to Analog #1 Output Offset)
Offset for scaling Analog Output Channel
#1.
voltage
output
channel
analog
GAIN
OUT
ANA
OFFSET
OUT
ANA
creates
software
drive
signal
% 0.0 -99.9 – 99.9
Y N
ANA 2 OUT
OFFSET
(Digital to Analog #2 Output Offset) Offset
for scaling Analog Output Channel #2.
voltage
output
channel
analog
GAIN
OUT
ANA
OFFSET
OUT
ANA
creates
software
drive
signal
% 0.0 -99.9 – 99.9
Y N
ANA 1 OUT
GAIN
(Digital to Analog #1 Output Gain)
Adjusts the scaling for the Analog Output
Channel #1.
NOTE: value of 1.0 = 0 to 10VDC signal.
voltage
output
channel
analog
GAIN
OUT
ANA
OFFSET
OUT
ANA
creates
software
drive
signal
none 1.0 0.0 – 10.0
Y N
ANA 2 OUT
GAIN
(Digital to Analog #2 Output Gain)
Adjusts the scaling for the Analog Output
Channel #2.
NOTE: value of 1.0 = 0 to 10VDC signal.
voltage
output
channel
analog
GAIN
OUT
ANA
OFFSET
OUT
ANA
creates
software
drive
signal
none 1.0 0.0 – 10.0
Y N
FLT RESET
DELAY
(Fault Reset Delay)
When the drive is
set for automatic fault reset, this is the
time before a fault is automatically reset.
sec 5 0 – 120
Y N
FLT RESETS /
HOUR
(Fault Resets per Hour)
When the drive
is set for automatic fault reset, this is the
number of faults allowed to be
automatically reset per hour.
faults 3 0 – 10
Y N