InstallationandOperationManual
4
TheFW106/FW106Ccanalsoconnectwithupto110panelsand/orremoteannunciatorsviaaCANbustoform
afireemergencydetectionandnotificationnetworksystem.
Networkedpanelsand/orannunciatorscansharethefollowingeventsandmanualcontrols:
Event(signal)type:ALA RM,SUPERVISORY,TROUBLE,MONITOR,OUTPUT
ManualControl
type:SignalSilence,BuzzerSilence,Reset,Acknowledge
Event/controlsharingcanbeconfiguredinthreemodes–PeertoPeer,Group,andMaster/Slave.
Peer‐to‐Peer
Allpanels/annunciatorsareintendedtofunctionasasinglesystemandshareevents/controlsofeach
other.
Group
Panels/annunciatorscanbeassigned
intomultiplegroups.Therearetwooptionsofevent/control
sharing:
o “Events&Operation”–Eventsandcontrolsareonlysharedwithinindividualgroup;Eventsand
ControlsareNOTsharedacrossthegroups.
o “Opera tionOnly ” –Eventsaresharedacrossthenetwork.Controlsaresharedwithinindividual
group.Each
panel/annunciatorcansilencetroubleslocallyoutsideofthegroup.
Master/Slave
o Onlyonepanel(address#1)canbetheMasterpanel.TheMaster panelcanreceiveeventsfromall
networkedpanels,aswellashavecontrolsoverallpanels.
o AlltheotherpanelsareSlavepanels. Aslavepanel
canonlyvieweventsfromitsowninputs,and
controlitsownoutputs.
o AllannunciatorsactliketheMasterpanel.