InstallationandOperationManual
7
SpecificationsandFeatures
ThespecificationsandfeaturesoftheFW106/FW106CControlPanelaredescribedinTable2.
Table2FW106/FW106CControlPanelSpecifications
General
Digitalsignalprocessorbaseddesign,fullyconfigurablefromfrontpanelwith
passwordprotection
Environmental
Operatingtemperature:32‐120F(0‐49C)
Relativehumidity: Upto93%@ 90F(32C)
Tobeinstalledinnormaldryindoorenvironment only
PrimarySupply
110‐120VAC60Hz(3.86A),or
220‐240VAC50Hz(1.96A)
SecondaryPower
Supply
Two12Vinserieslead‐acidbatteriesset
Chargingcapacity:40AH
PowerOutputs
Internalpowersupplyfor
AMI
ALUsandAddressableLoopCircuits
NOUsandNotificationApplianceCircuits
XNUs,ExternalNetworkCircuits
ROUs
Oneauxiliarypowersupply
Non‐Resettable/ResettablePowerOutput(configurable)
Powerlimited
24VDC
Outputcurrent:500mAinnormalstandby,1200mAinalarm
PowerFactorRating:0.35
Specialapplication:CompatibledevicesaretheAnnunciator ModelFW121/
FW121C/FW122W/FW122R/FW122CW/FW122CR/FW123/FW123CandIO
ModuleModelFW821.
RelaysOutput
Oneprogrammablerelay
4non‐programmablestatusrelays
Status:Alarm,Supervisory,Trouble,Monitor
FormCContact
ContactRating:2A30VDC
PowerFactorRation:0.35
NotificationAppliance
Circuits
Totalof10circuitssupported,totalpoweravailable8A
2ClassAor2ClassBcircuitsoneachNOU
MaximumCurrent:2AperNACcircuit
AlarmVoltage:24Vnominal
Bellcode:Temporal3
Panelsupportsoneregulated24VDCNAC,orupto10specialapplication24VDC
NAC.RefertoTable20forspecificappliances/devices.
Maxlineloss:1.8V.