InstallationandOperationManual
60
Appendix‐C:QuantitiesofNotificationAppliances
Table19liststhemaximumnumberofnotificationappliances(FW961R/FW961W,FW971R/FW971W,
FW981R/FW981W,FW962R/FW962W,andFW982R/FW982W)perNACintheworstcasescenariofor
Synchronizationsystem.
Table19MaximumNumbersofNA
ModelNo. Description MaximumnumberperNAC
FW961R/FW961W Horn/StrobeLight 15
FW971R/FW971W Horn 110
FW981R/FW981W StrobeLight 16
FW962R/FW962W Multi‐candel aHornStrobe 33
FW982R/FW982W Multi‐candela Strobe 33
Ifthese3typesofnotificationappliancesaremixedinthesamecircuit,thetotal
currentofthecircuitmustbe<=2Amperes.