RefertoTable7fortroubleeventtypesandexplanationoftheevents.
Table7TroubleEventType
Category TroubleEventType Explanation
System
PrimaryPower_Loss Primarypowerislost
Battery_Loss Batteryislost
ControlPanel_Grounding Controlpaneldetectsgroundcondition
PrimaryPower_OverVoltage Primarypowervoltageistoohigh
Charger_OverVoltage Chargervoltageistoohigh
ArchiveFile_Missing Historyrecordfileismissing
ConfigFile_Missing Configurationfileismissing
ConfigFile_Damaged Configurationfileisdamaged
Unit
ALU_Conf.Mismatch ALU’sconfigurationfileismismatchedwith
AMI’s
AMI_Jumper AMIhasajumpershorted
Unit_Missing PCU/ALU/NOU/ROU/XNUismissing
Ext._Missing Thenetworkannunciatorismissing
Unit_Addr.Conflict 1.TwoormoreALUshavethesame
addresses,or
2.TwoNOUshavethesameaddresses
Unit_Illegal Theunitisworking,butitisnotconfigured
Unit_SwitchError Theunitaddresschangedduringrunning
Circuit
Ext._Illegal Thenetworkannunciatorisworking,butitis
notconfigured
Ext._Grounding Thenetworkcircuitisgrounded
Ext.__Addr.Conflict Twoormoreannunciatorsonthenetwork
circuithavethesameaddress
Bus_Short Theaddressableloopcircuitisshorted

Table of Contents