InstallationandOperationManual
58

AppendixB:WireSelectionGuide
SLCWireSelectionGuide
MaximumLoopCurrent=100mA@NSB,220mA@Alarm
MaximumLoopCapacitance=0.1uF
Table16AddressableLoopWiring
WireGauge MaximumWiringRuntoLastDevice
(AWG)
Wire
Resistance
ohms/km
Maximumcurrent
90mA
Maximumcurrent
150mA
Maximumcurrent
220mA
ft m ft m ft m
12 5.31 15099 4603 9060 2762 6177 1883
13 6.69 11985 3654 7191 2192 4903 1495
14 8.45 9488 2893 5693 1736 3882 1183
15 10.6 7564 2306 4538 1384 3094 943
16 13.5 5939 1811 3563 1086 2430 741
17 16.3 4919 1500 2951 900 2012 613
18 21.4 3747 1142 2248 685 1533 467