InstallationandOperationManual
48

OnAnnunciator:
Indicatesthatthepowerworksnormally.
OFF
OncontrolPanel:
Indicates that the system is not powered on
yetorthesystemispoweredbybattery .
OnAnnunciator:
Indicates that the system is not powered on
yet.
SIGNALSILENCE
Yellow
SteadyON
IndicatesthatthereareactivatedNACdevices
andatleastoneofthemhasbeensilenced.
OFF
Indicates that there is no NAC activated or a
NACisactivatedandnotsilenced.
GROUNDFAULT
Yellow
SteadyON
IndicatesthatthereareGroundFaulteventsin
thesystem.
OFF
Indicates that there is no Ground Fault event
inthesystem.
BYPASS
Yellow
SteadyON Indicatesthattherearedisabledevents.
OFF Indicatesthattherearenodisabledevents.
CPUFAULT
Yellow
SteadyON IndicatesthattheCPUisinfault.
OFF IndicatesthatthereisnoCPUfault.
BuzzerOperation
Thebuzzeroperatesasfollows:
Normally OFF indicates that the system is in normal condition or all events in the system have been
acknowledged.
ON(continuous)indicatesthatatleastONEunacknowledgedalarmispresentinthesystem.
ON(1pulseper0.25second)indicatesthatatleast
ONEunacknowledgedAlerteventispresentinthesystem
ON (1 pulse per 0.5 second) indicatesthat at leastONEunacknowledgedsupervisory event is present in the
system.
ON(1pulseper1second)indicatesthatatleastONEunacknowledgedtroubleeventispresentinthesystem.
ON
(1 pulse per 2 second) indicates that at least ONE unacknowledged other signal event is present in the
system.
