EasyManua.ls Logo

Maple Armor FW106C - Battery Capacity; Table 21 Battery Calculation

Default Icon
73 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InstallationandOperationManual
63

EOL× 0.00082 0.00082
AuxiliaryPowerSupply Standby Alarm
TotalCurrents Standby Alarm
BatteryCapacity
Table21BatteryCalculation
TotalStandbyCurrent
(fromabove)
HoursofStandbyRequiredperUL864Standard AHforStandby
A x24Hours =
TotalAlarmCurrent
(fromabove)
5MinutesofAlarmOperation
per UL864 Standard, 30 Minutes of Alarm
OperationperULCS527and5MinutesofAlert
forTwostage.
AHforAlarm
A
x0.09Hours
(ForULcompliance)
=
A
x0.6Hours
(ForULCcompliance)
=
A.H.forStandby A.H.forAlarm CalculatedA.H. Derating
Factor
A.H.RequiredBattery
Capacity
+ = X1.25 =
Maximumavailablebatteryspace:
Length:8.07in.,width:6.61in.,height:7.87in.
Maximumbatterycapacity:40AH
Notes:
Useofalternativebatteriesmayresultinfailureofthepaneltomeetagencyandregulatoryrequirementsand
mayresultinshortenedbatterylife.Batteriesshouldbetestedregularlyandreplacedatleasteveryfouryears.