TSC 900 TRANSFER SWITCH CONTROLLER
PM 151 REV 1 15/10/08 Thomson Power Systems
4.7. TIMER BYPASS
The following automatic sequencing time delays can be temporarily bypassed when the time
function is active as shown on the TSC 900 GHC display:
Utility Return Timer
Cooldown Timer
Warm up Timer
Neutral Delay Timer
This feature is typically used when testing to avoid waiting for the complete duration of the
time period. To activate the bypass function, press the BYPASS button when the timer is in
operation as displayed on the screen.
NOTE: The Time delay functions will return to the normal time settings on the subsequent
automatic operating sequence.