Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13
User’s Manual Page 33 of 36
11.2 On-Off Logic
Relay type
PV
Relay
LED
Hi-On
PV > SP
On
On
PV < SP
Off
Off
Open sensor
Up scale
On
On
Down scale
Off
Off
Low-On
PV > SP
Off
Off
PV < SP
On
On
Open sensor
Up scale
Off
Off
Down scale
On
On
11.3 Retramission Output Table for Open /Over /Under Condition
(Applicable only for LC5296, LC5296-H, 5006-RN)
RETRASMISSION
VARIABLE
SCALE
ACTION
OPEN
OVER
UNDER
4-20mA
PV
UP
DIR
20.8
20.8
3.2
PV
DOWN
REV
20.8
3.2
20.8
PV
UP
REV
3.2
3.2
20.8
PV
DOWN
DIR
3.2
20.8
3.2
1-5V
PV
UP
DIR
5.2V
5.2V
0.8V
PV
DOWN
REV
5.2V
0.8V
5.2V
PV
UP
REV
0.8V
0.8V
5.2V
PV
DOWN
DIR
0.8V
5.2V
0.8V
NOTE: -1. OPEN/UNDER/OVER condition is applicable to all input types except
0-5v / 0-20mA.