EasyManua.ls Logo

Masibus LC5296 - 11.2 On-Off Logic; 11.3 Retramission Output Table for Open;Over;Under Condition

Masibus LC5296
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13
User’s Manual Page 33 of 36
11.2 On-Off Logic
Relay type
PV
Relay
LED
Hi-On
PV > SP
On
On
PV < SP
Off
Off
Open sensor
Up scale
On
On
Down scale
Off
Off
Low-On
PV > SP
Off
Off
PV < SP
On
On
Open sensor
Up scale
Off
Off
Down scale
On
On
11.3 Retramission Output Table for Open /Over /Under Condition
(Applicable only for LC5296, LC5296-H, 5006-RN)
RETRASMISSION
VARIABLE
SCALE
ACTION
OPEN
OVER
UNDER
4-20mA
PV
UP
DIR
20.8
20.8
3.2
PV
DOWN
REV
20.8
3.2
20.8
PV
UP
REV
3.2
3.2
20.8
PV
DOWN
DIR
3.2
20.8
3.2
1-5V
PV
UP
DIR
5.2V
5.2V
0.8V
PV
DOWN
REV
5.2V
0.8V
5.2V
PV
UP
REV
0.8V
0.8V
5.2V
PV
DOWN
DIR
0.8V
5.2V
0.8V
NOTE: -1. OPEN/UNDER/OVER condition is applicable to all input types except
0-5v / 0-20mA.