SETTINGS
EN / Mass Combi 12/2500-100; 24/2500-60; 48/2500-35; 48/5000-70 / May 2010 29
6 SETTINGS
The Mass Combi is provided with two groups of DIP-switches to adjust the apparatus according to the specifications of the
electrical installation. The DIP-switches are located in the connection compartment. See figure 31.
6.1 DIP SWITCH A
6.1.1 Parallel mode
If you want… DIP switch A
SW1 SW2
to configure the Combi as Master (Combi A) then… OFF OFF
to configure the Combi as Slave (Combi B) then… ON ON
to configure the Combi as Slave (Combi B) having its own charge characteristics then…
(only when both Combi A and Combi B have their own battery set)
OFF ON
NOTES:
If the Combi is configured as Slave, then the settings of SW3 to SW8 of DIP switch A and SW1 to SW7 of DIP switch B are
denied.
If the charge characteristics of the Combi that is configured as Slave (Combi B) are set to follow the Master (DIP Switch A:
SW1= ON) then its settings SW6 to SW7 of DIP switch A are denied.
6.1.2 Output frequency inverter
230V Models DIP switch A
If you want… SW3
to set the output frequency to 50 Hz OFF
to set the output frequency to 60Hz ON
Figure 31: DIP switches
DIP switch A
DIP switch B
SW
ON
OFF
1 2 4 6 53 7
8
SW
ON
OFF
1 2 4 6 53 7
8