8.3.4 List of list of event commands
Below is shown the list of event commands and event data of the Mass Combi. Other devices connected to the MasterBus can
be programmed to initiate these commands and actions at the Mass Combi.
Event command Event data Description
On The AC-input current will be limited by the ”Generator limit” setting; see section
8.3.1, “Input Select”
Off The AC-input current will be limited by the “Shore Fuse” setting
Toggle Limitation of the AC-input current toggles between ”Generator limit” and “Shore
Fuse”
Copy Invert If the Event Source switches to “On”, the AC-input current will be limited by the
“Shore Fuse” setting; If the Event Source switches to “Off”, the AC-input
current will be limited by the ”Generator limit” setting.
Input select
Copy If the Event Source switches to “On”, the AC-input current will be limited by the
”Generator limit” setting; If the Event Source switches to “Off”, the AC-input
current will be limited by the “Shore Fuse” setting.
On Operation mode of the Mass Combi will be set to “Auto”, see section 8.3.1,
“Mode”
Off Operation mode of the Mass Combi will be set to “Charger”.
Toggle Operation mode of the Mass Combi toggles between “Auto” and “Charger”
Copy Invert If the Event Source switches to “On”, the Operation mode of the Mass Combi
will be set to “Charger”; If the Event Source switches to “Off”, the Operation
mode of the Mass Combi will be set to “Auto”.
Mode
Copy If the Event Source switches to “On”, the Operation mode of the Mass Combi
will be set to “Auto”; If the Event Source switches to “Off”, the Operation mode
of the Mass Combi will be set to “Charger”.