72
SVERKER 750/760
Programma Electric AB
ZP-CD01E R05A
9.6 Other
Injection
Maintained
Injection continues without any time limitation.
Momentary
Injection continues only as long as be button is kept
depressed.
Minimum momentary injection time is 0.1 s.
Max time
Injection stops automatically when the preset
maximum time is reached.
Max injection time: 99.9 s.
Resolution at max time: 0.1 s.
Filtering
If filtering was selected, five successive readings are
averaged. The following can be filtered:
• Current
• Voltage
• Extra items that are measured
Off delay
The turning off of generation can be delayed after
tripping throughout a specified time interval that is
expressed in mains-frequency cycles.
Max off delay: 999 mains-frequency cycles.
Resolution at max off delay: 1 cycle.
Memories
There are four memories numbered 0 through 3.
Languages
The menus, prompts etc. can be expressed in one of
five languages: English, German, French, Spanish or
Swedish.
Set of resistors
egamhorotsiseRtnerrucxaM
5.0 Ω A01
1 Ω A7
52 Ω A2
001 Ω A7.0
005 Ω A3.0
k1 Ω A22.0
k5.2 Ω A11.0
Capacitor (Sverker 750)
Capacitance: 10 μF
Max voltage: 450 V AC
Mains
egatlovsniaMtupnI.xaM
tnerruc
sniamdetaR
seicneuqerf
%01±CAV032A6zH06-05
%01±CAV511A21zH06-05
Weight
057rekrevS067rekrevSesactropsnarT
)sbl1.83(gk3.71)sbl5.93(gk9.71)sbl6.71(gk0.8
Dimensions
067/057rekrevSesactropsnarT
htdiW)''8.31(mm053)''0.42(mm016
htpeD)''6.01(mm072)''8.01(mm572
thgieH)''7.8(mm022)''8.31(mm053
Ambient temperatures
During use
0 to +50°C ( +32 to +122°F)
During transportation
-40 to +70°C ( -40 to +158°F)