134
It is only valid for the input terminals X6. It is used together with P02.04=4 to serve as the reference of the
main frequency. The relation between the input signal pulse frequency and the set frequency can be
adjusted through the curve of Group P10.
13: Auxiliary set frequency pulse input (valid only for X6)
It is only valid for the input terminals X6. It is used together with P02.04=4 to serve as the reference of the
auxiliary frequency. The relation between the input signal pulse frequency and the set frequency can be
adjusted through the curve of Group P10.
14: Frequency increase command (UP)
15: Frequency decrease command (DN)
The remote control of the frequency increase or decrease is realized through control terminals rather than
operation panel. It is enabled when P02.04=1 (common operation) or P02.07=2 (as auxiliary frequency).
The acceleration/ deceleration rate is set by P09.09.
16: External equipment fault normally open input
17: External equipment fault normally closed input
The fault signal of external equipments can be input through this terminal for monitoring fault of external
equipments by the drive. The drive will display “Er.EFT” ( i.e. external equipment fault alarm) upon
receiving the fault signal of external equipments; and such signals can adopt either the input mode of
normally open or normally closed.
18: External interrupt normally open contact input
19: External interrupt normally closed contact input
The drive will lock the output and run with zero frequency when receiving the external interrupt signal
during running. Once the external interrupt signal is removed, the drive will start in the speed tracking
mode and resume the running.
20: Reference frequency source switching command
The reference frequency source can realize the reference mode of the frequency source through this
terminal function and the function code of P02.10.
21: Reserved
22: External reset input
Realizing the fault reset. The STOP/REST key on the operation panel and the host device command can
be used to reset the fault as well.
23: Coast to stop input (FRS)
In the running status, once this terminal function is enabled, the drive will coast to stop immediately.
24: Acceleration/deceleration disable command
If this function terminal is enabled, the running frequency will remain the same, except for the stop
command.
25: Stop DC braking input command
Once the drive received the stop command, when the running frequency is lower than the stop DC
braking frequency P08.12, the drive will start the DC braking. The braking current is set by P08.14 and