136
ON ON OFF
Process closed loop PID
ON ON ON
Multi-speed
34: Main reference frequency source selection 1
35: Main reference frequency source selection 2
36: Main reference frequency source selection 3
The switching of the frequency reference channels in Table 6-10 can be realized by selecting the
ON/OFF combination of terminal 1, 2, and 3 through the frequency reference channels. It is enabled
when the relation between the terminal switching and the function code P02.04 is “later comer”.
37: Switching main reference frequency to AI
The main set frequency channel will be switched to AI reference when this function terminal is enabled.
The choosing of AI shall be set in the AI function of Group P10.01. The frequency reference channel will
be restored when this function terminal is disabled.
38: Command source selection 1
39: Command source selection 2
The running command channel selection in Table 6-11 can be realized by selecting the ON/OFF
combination of the command source selection terminals 1 and 2.
Table 6-11 Running command channel selection
Selecting terminal 2 as
command source
Selecting terminal 1 as
command source
Running command channel
OFF OFF
Running command channel
maintained
OFF ON
Operation panel running
command channel
ON OFF
Terminal running command
channel
ON ON
Serial port running command
channel
40: Switching command to terminal
When this function terminal is enabled, the running command channel will be switched to the terminal
running command channel. When this function terminal is disabled, the running command channel will
return to the original state.
41: FWD disabled
42: REV disabled
FWD disabled: If this terminal is enabled during the forward running, the drive will coast to stop. If this
terminal is enabled before the forward running, the drive will enter the zero-frequency running state. The
reverse running will not be affected.
REV disabled: Similarly.
43: Drive running disabled
The drive will coast to stop once this function code is enabled; the drive will start normally once this