MI 3125 EurotestCOMBO Technical specification
52
Prospective fault current (calculated value)
Measuring range (A) Resolution (A) Accuracy
0.00 ÷ 9.99
0.01
10.0 ÷ 99.9
0.1
100 ÷ 999
1
1.00k ÷ 9.99k
10
10.0k ÷ 23.0k
100
Consider accuracy of fault
loop resistance
measurement
The accuracy is valid if mains voltage is stabile during the measurement.
Test current (at 230 V)...................... 6.5 A (10 ms)
Nominal voltage range...................... 30 V ÷ 500 V (45 Hz ÷ 65 Hz)
7.4.2 RCD selected
Fault loop impedance
Measuring range according to EN61557 is 0.46 Ω ÷ 9.99 kΩ.
Measuring range (Ω) Resolution (Ω)
Accuracy
0.00 ÷ 9.99
0.01
10.0 ÷ 99.9
0.1
±(5 % of reading + 10 digits)
100 ÷ 999
1
1.00k ÷ 9.99k
10
± 10 % of reading
Accuracy may be impaired in case of heavy noise on mains voltage
Prospective fault current (calculated value)
Measuring range (A) Resolution (A) Accuracy
0.00 ÷ 9.99
0.01
10.0 ÷ 99.9
0.1
100 ÷ 999
1
1.00k ÷ 9.99k
10
10.0k ÷ 23.0k
100
Consider accuracy of fault
loop resistance
measurement
Nominal voltage range...................... 30 V ÷ 500 V (45 Hz ÷ 65 Hz)
No trip out of RCD.
R, XL values are indicative.
7.5 Line impedance and prospective short-circuit current
Line impedance
Measuring range according to EN61557 is 0.25 Ω ÷ 9.99kΩ.
Measuring range (Ω) Resolution (Ω)
Accuracy
0.00 ÷ 9.99
0.01
10.0 ÷ 99.9
0.1
±(5 % of reading + 5 digits)
100 ÷ 999
1
1.00k ÷ 9.99k
10
± 10 % of reading

Table of Contents

Other manuals for METREL MI 3125

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the METREL MI 3125 and is the answer not in the manual?

METREL MI 3125 Specifications

General IconGeneral
TypeMultifunction Installation Tester
Insulation ResistanceYes
Continuity TestYes
Loop ImpedanceYes
RCD TestingYes
Voltage MeasurementYes
Frequency MeasurementYes
DisplayLCD
Power Supply6 x 1.5 V AA batteries
Loop Resistance Resolution0.01 Ω
Frequency45 - 65 Hz
Line Voltage Resolution1 V
Insulation Resistance Test Voltage50 V, 100 V, 250 V, 500 V, 1000 V
Insulation Resistance Resolution0.01 MΩ
Continuity Resistance Resolution0.01 Ω
Test Current200 mA
DC VoltageUp to 600 V
Loop Resistance0.0 Ω - 1999 Ω
Line VoltageUp to 550 V
Line Voltage Accuracy±2% ±2 digits
Rated Residual Current10 mA, 30 mA, 100 mA, 300 mA, 500 mA
Insulation Resistance Range0.01 MΩ to 1 TΩ
Continuity Resistance0.0 Ω - 1999 Ω
Dimensions220 x 103 x 55 mm
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to +60°C
Safety StandardsEN 61557
Loop Resistance Accuracy±(5% + 3 digits)