Command Mode - Configuration & Operation
12
Panel Configuration/Features/Auxiliary disconnect, disconnects alarm and supervisory relay
If enabled the auxiliary disconnect operation, disconnects alarm and supervisory relays disabled the auxiliary
disconnect operation has no affect on the alarm and supervisory relays. Default is disabled.
Panel Configuration/Features/Signal silence inhibit timer
Select the timer value for the signal silence inhibit timer
Panel Configuration/Features/Auto signal silence timer
Select timer value for the auto signal silence timer
Panel Configuration/Features/Number of remote annunciators
The screen will ask if the panel is an LCD or LED, then the following menu will show up for either.
Select the number of remote annunciators.
Panel Configuration/Features/Alarm transmit silence
This feature allows the alarm transmits and auxiliary alarm relay to reset on “SIGNAL SILENCE” rather than the
“RESET” switch if enabled. Default is disabled.
Note: Addresses available for remote annunciators are 1 through to and including 7. Please note that the
LED remote annunciators MUST have lower value addresses than any LCD remote annunciators.
$X['LV 'LV$OP 6SY
>@ (QDEOHG
Sig-sil.inhibit tmr .
[X] Disabled
[ ] 10 sec
[ ] 20 sec
[ ] 30 sec
[ ] 1 min
Auto sig .sil. timer
[X] Disabled
[ ] 5 min
[ ] 10 min
[ ] 15 min
[ ] 20 min
[ ] 30 min
No. of remote annun .
[X] None
[ ] 1
[ ] 2
[ ] 3
[ ] 4
[ ] 5
[ ] 6
[ ] 7
[ ] 8
$OP[PLW VLO
>@ (QDEOHG