CHAPTER 8 FUNCTIONS
8
8.10 Alert Output Function (Process Alarm)
(6) Setting procedure
The setting procedure for the main A/D converter module is as follows:
1. Set "Method selection" to "Parameter write".
"CC IE Field Configuration" window Select the main A/D converter module from "List of stations"
[CC IE Field Configuration] [Online] [Parameter Processing of Slave Station]
2. In "Basic module parameter", set "CH A/D conversion enable/disable setting" to "0: Enable".
3. In "Basic module parameter", set "CH Alert output setting" to "0: Enable".
4. In "Basic module parameter", specify the values for "CH; Process alarm upper upper limit
value", "CH Process alarm upper lower limit value", "CH Process alarm lower upper limit
value", and "CH Process alarm lower lower limit value".
Alert output function must meet the following condition:
Process alarm upper upper limit value Process alarm upper lower limit value Process alarm lower upper limit value
Process alarm lower lower limit value
For the extension A/D converter module, make the settings for each item of "Ext. module 1_Module parameter".
Item Setting range
CH Process alarm upper upper limit value
-32768 to 32767
CH Process alarm upper lower limit value
CH Process alarm lower upper limit value
CH Process alarm lower lower limit value