110
(4) Example of the scaling setting
1: For the channel with the set input range of 0 to 5V, of the main A/D converter module, settings are
made as follows:
•"CH Scaling enable/disable setting": "0: Enable"
•"CH Scaling upper limit value": 12000
•"CH Scaling lower limit value": 4000
The digital output value and the digital operation value would be as follows:
Analog input voltage (V) Digital output value Digital operation value
0 0 4000
1 3200 5600
2 6400 7200
3 9600 8800
4 12800 10400
5 16000 12000
Digital output value
16000
0
50
Analog input voltage (V)
Scaling upper limit value
12000
Scaling lower limit value
4000