112
Ex.
3: For the channel with the set user range of 2 to 10V, of the main A/D converter module, settings are
made as follows:
•"CH Scaling enable/disable setting": "0: Enable"
•"CH Scaling upper limit value": 12000
•"CH Scaling lower limit value": 4000
The digital output value and the digital operation value would be as follows:
Analog input voltage (V) Digital output value Digital operation value
-6 -16000 -4000
-4 -12000 -2000
-2 -8000 0
0 -4000 2000
2 0 4000
4 4000 6000
6 8000 8000
8 12000 10000
10 16000 12000
16000
12000
-6 0 2 10
0
2000
4000
Analog input voltage (V)
Digital output value
-16000
-4000
Scaling upper limit value: 12000
Scaling lower limit value: 4000
Digital
operation
value
Digital output value