(3) Example of the combined use of the digital clipping function and the scaling
function
For the channel with the set input range of 0 to 5V, of the main A/D converter module, settings are made
as follows:
•"CH Scaling enable/disable setting": "0: Enable"
•"CH Scaling upper limit value": 24000
•"CH Scaling lower limit value": 0
•"CH Digital clipping enable/disable setting": "0: Enable"
1. Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window Select the main A/D converter module from "List of stations"
[CC IE Field Configuration] [Online] [Parameter Processing of Slave Station]
2. In "Basic module parameter", set "CH A/D conversion enable/disable setting" to "0: Enable".
Input voltage (V) Digital output value Digital operation value
-0.12 -384 0
00 0
1 3200 4800
2 6400 9600
3 9600 14400
4 12800 19200
5 16000 24000
5.12 16383 24000
1) Digital output value
Digital clipping
Output range: -384 to 16383
Output range: 0 to 16000
0
0
5
Analog input voltage (V)
Digital output value
1) Digital output value
3) Digital operation value
2) Value after digital clipping
3) Digital operation value
2) Value after digital clipping
Scaling
Upper limit value: 16000 24000
Lower limit value: 0 0
16000
16383
24000
-384